Windis

Windis Ceil 500

Recessed ceiling air curtain

The water-heated Windis Ceil 500 is recessed into the suspended ceiling, for industrial and logistics buildings whose entrance has a suspended ceiling. The 500 series covers doorways up to 5 metres high. Available in five nominal sizes: 1 m, 1.5 m, 2 m, 2.5 m and 3 m. The ceiling recess is 350 mm deep.

Windis Ceil 500

An integrated controller is included as standard and connects to the building management system. On water-heated units, energy metering is part of the standard delivery.

Water heating, electric heating or no heating can be chosen. Site-specific sizing and dimension drawings come from Windis Select.

Features

Energy metering, the heating valve and heating-network pressure measurement apply to water-heated models.

Performance

  • Integrated thermal energy metering
  • Adjustable discharge impulse
  • EC fans

Installation

  • Quick connectors for external sensors
  • Integrated heating valve

Connectivity and monitoring

  • Modbus TCP and BACnet IP interface
  • Heating network pressure measurement
  • Built-in frost risk detection

Construction

  • Colours: body RAL 7035, grille RAL 7024, other RAL colours available to order
  • Fan: EC centrifugal fans, ball bearings
  • Heating coil: copper tubes 3/8", aluminium fins, max 6 bar @ 100 °C
  • Electrical connections: power supply cable 2 m, earthed plug
  • Other connections: M12 connectors, Ethernet, USB

Scope of delivery

Integrated inside the unit:

  • Energy metering (ultrasonic flow measurement)
  • 2-way heating valve, Belimo C215Q-J / C220Q-K
  • actuator with 15 s running time
  • discharge impulse control
  • water in/out temperature measurement
  • air in/out temperature measurement
  • freeze risk detection
  • heating network pressure measurement
  • air bubble detection
  • G4 filter

Interfaces: Modbus TCP, BACnet IP, Modbus RTU/BACnet MSTP, I/O.

Optional: filter differential-pressure measurement.

Technical data

Models: Ceil 500-100 · Ceil 500-150 · Ceil 500-200 · Ceil 500-250 · Ceil 500-300

Performance ranges, water heating

Scroll the table sideways

Water temperatureHeating capacity (kW)Water flow (l/s)Pressure drop (kPa)
70/40 °C19,1 – 60,10,152 – 0,4793,7 – 8,5
60/30 °C8,0 – 37,20,064 – 0,2971,6 – 5,3
50/30 °C9,0 – 32,50,108 – 0,3892,6 – 6,9

Discharge air temperature 20 °C. The ranges cover all five widths (1 m – 3 m) and the fan control range 20–100 %.

The pressure drop applies to the heat exchanger. The site-specific operating point and pressure drop come from Select.

Exact site-specific sizing is done in Windis Select. The values shown are control ranges per series.

Airflow, sound pressure and fan

Scroll the table sideways

Airflow (m³/h)Sound pressure level (dBA)Fan input power (W)
341 – 7 80037,3 – 92,0460 – 1 380

The ranges cover all five widths (1 m – 3 m) and the full fan control range 20–100 %.

Sound pressure level LpA, Sabine 10 m². Alternative reporting 5 m / 200 m² (≈ –8 dB) for Free/Ceil 350 models in Select.

500-series fan input power as nameplate values (Max. Input Power, Free Air). Per width: 1 m = 460 W (2 pcs), 1.5 m = 690 W (3 pcs), 2 m and 2.5 m = 920 W (4 pcs), 3 m = 1,380 W (6 pcs). Actual consumption in installed conditions is lower.

Model sizes

Scroll the table sideways

ModelNominal width (m)Height (mm)
Ceil 500-1001,0350
Ceil 500-1501,5350
Ceil 500-2002,0350
Ceil 500-2502,5350
Ceil 500-3003,0350

The nominal width is the model size, not the casing's outer dimension.

Exact outer dimensions, installation openings, weights and mounting details for the Ceil 500 series will be added once the first manufactured units have been measured.

Detailed dimension drawings per model are available in Windis Select.

Downloads

Size your project in Windis Select

Enter the door dimensions, the conditions and the heating type, and Select calculates the performance values and produces the documents for the design. Help with choosing the size class is available directly from Windis.