Windis

Windis Vertical 500

Vertically mounted air curtain

The water-heated Windis Vertical 500 is mounted vertically at the side of the doorway, for tall and wide industrial doors. The recommended doorway width is 5 metres when units are installed on both sides of the door. Available in five heights: 1 m, 1.5 m, 2 m, 2.5 m and 3 m.

Windis Vertical 500

Units can be stacked on top of each other to cover a taller opening, for example 3 metres and 2 metres stacked to cover a height of 5 metres.

An integrated controller is included as standard and connects to the building management system. Also available in stainless steel.

Features

Energy metering, the heating valve and heating-network pressure measurement apply to water-heated models.

Performance

  • Integrated thermal energy metering
  • Adjustable discharge impulse
  • EC fans

Installation

  • Quick connectors for external sensors
  • Integrated heating valve

Connectivity and monitoring

  • Modbus TCP and BACnet IP interface
  • Heating network pressure measurement
  • Built-in frost risk detection

Construction

  • Colours: body RAL 7035, grille RAL 7024, other RAL colours available to order
  • Fan: EC centrifugal fans, ball bearings
  • Heating coil: copper tubes 3/8", aluminium fins, max 6 bar @ 100 °C
  • Electrical connections: power supply cable 2 m, earthed plug
  • Other connections: M12 connectors, Ethernet, USB

Scope of delivery

Integrated inside the unit:

  • Energy metering (ultrasonic flow measurement)
  • 2-way heating valve, Belimo C215Q-J / C220Q-K
  • actuator with 15 s running time
  • discharge impulse control
  • water in/out temperature measurement
  • air in/out temperature measurement
  • freeze risk detection
  • heating network pressure measurement
  • air bubble detection
  • G4 filter

Interfaces: Modbus TCP, BACnet IP, Modbus RTU/BACnet MSTP, I/O.

Optional: filter differential-pressure measurement.

Technical data

Models: Vertical 500-100 · Vertical 500-150 · Vertical 500-200 · Vertical 500-250 · Vertical 500-300

Performance ranges, water heating

Scroll the table sideways

Water temperatureHeating capacity (kW)Water flow (l/s)Pressure drop (kPa)
70/40 °C19,1 – 60,10,152 – 0,4793,7 – 8,5
60/30 °C8,0 – 37,20,064 – 0,2971,6 – 5,3
50/30 °C9,0 – 32,50,108 – 0,3892,6 – 6,9

Vertical models' performance corresponds to the Free model of the same power class. Vertical sizing is done site-specifically in Select.

Discharge air temperature 20 °C. The ranges cover all five widths (1 m – 3 m) and the fan control range 20–100 %.

The pressure drop applies to the heat exchanger. The site-specific operating point and pressure drop come from Select.

Exact site-specific sizing is done in Windis Select. The values shown are control ranges per series.

Airflow, sound pressure and fan

Scroll the table sideways

Airflow (m³/h)Sound pressure level (dBA)Fan input power (W)
341 – 7 80037,3 – 92,0460 – 1 380

Vertical models' performance corresponds to the Free model of the same power class. Vertical sizing is done site-specifically in Select.

The ranges cover all five widths (1 m – 3 m) and the full fan control range 20–100 %.

Sound pressure level LpA, Sabine 10 m². Alternative reporting 5 m / 200 m² (≈ –8 dB) for Free/Ceil 350 models in Select.

500-series fan input power as nameplate values (Max. Input Power, Free Air). Per width: 1 m = 460 W (2 pcs), 1.5 m = 690 W (3 pcs), 2 m and 2.5 m = 920 W (4 pcs), 3 m = 1,380 W (6 pcs). Actual consumption in installed conditions is lower.

Dimensions and weights

Scroll the table sideways

ModelHeight (mm)Width (mm)Depth (mm)Weight (kg)
Vertical 500-100980350550–
Vertical 500-1501 48035055077
Vertical 500-2001 98035055095
Vertical 500-2502 480350550108
Vertical 500-3002 980350550–

Vertical weights are indicative.

Vertical 500-100 and Vertical 500-300 weights to be completed.

Detailed dimension drawings per model are available in Windis Select.

Downloads

Size your project in Windis Select

Enter the door dimensions, the conditions and the heating type, and Select calculates the performance values and produces the documents for the design. Help with choosing the size class is available directly from Windis.